Testing Komunikasi Modbus RTU VFD Vacon 10 Menggunakan Modbus Poll

1️ Tujuan

    1. Menguji koneksi komunikasi Modbus RTU antara PC/Laptop dan VFD Vacon 10
    2. Membaca data feedback VFD (frekuensi, speed, arus, status)
    3. Memberikan perintah RUN / STOP dan setpoint frekuensi melalui Modbus

2️ Peralatan

No Alat
1 VFD Vacon 10
2 Motor 3 phase
3 PC / Laptop
4 USB to RS485 Converter
5 Software Modbus Poll
6 Kabel RS485 (A+, B−, GND)
7 Sumber listrik VFD

3️ Wiring Dasar

 

🔹 Power VFD (sesuai gambar)

        • L1 – L2/N – L3 → Sumber listrik
        • U/T1 – V/T2 – W/T3 → Motor
        • Ground motor & VFD wajib tersambung (360° earthing)

🔹 Komunikasi RS485

USB–RS485

Vacon 10

A(+)

RS485 +

B(−)

RS485 −

GND

GND (jika tersedia)

⚠️ Pastikan tidak terbalik A/B, karena menyebabkan timeout.

4️ Setting Parameter VFD (Quick Modbus Setup)

🔧 Parameter di keypad Vacon 10

STEP 1 – Aktifkan kontrol via Fieldbus

      • P2.1 = 1 → Control place = Fieldbus

STEP 2 – Setting dasar komunikasi
(Sesuaikan dengan Modbus Poll)

      • Slave ID → contoh: 1
      • Baudrate → 9600 / 19200
      • Data bit → 8
      • Parity → None
      • Stop bit → 1

5️ Konfigurasi Modbus Poll

    1. Buka Modbus Poll
    2. Menu Connection → Connect
    3. Pilih:
      • Connection: RTU
      • COM Port: sesuai USB–RS485
      • Baudrate: sama dengan VFD
      • Parity: None
      • Slave ID: 1
    4. Klik OK

Jika benar → Tx/Rx counter bertambah

6️ Testing Output Data (Read Register)

Gunakan Holding Register (4xxxx) atau Input Register (3xxxx) sesuai tabel.

📋 Tabel Register Output Vacon 10

Fungsi Register Keterangan
FB Status Word 32101 / 42101 Status RUN/STOP
FB Actual Speed 32103 % speed
Motor Frequency 32104 Hz
Motor Speed 32105 RPM
Motor Current 32106 Ampere
Motor Torque 32107 %
Motor Power 32108 %
Motor Voltage 32109 Volt
DC Voltage 32110 DC Bus
Active Fault 32111 Kode fault

🔍 Contoh di Modbus Poll

    • Address: 32101
    • Quantity: 11
    • Function: Read Input Registers (04)

7️ Contoh Perhitungan Scaling

Data Nilai Register Scale Nilai Aktual
Actual Speed 5000 0,01 50,00 %
Motor Freq 2500 0,01 25,00 Hz
Motor Speed 744 1 744 RPM
Motor Torque 19 0,1 1,9 %
DC Voltage 1105 1 1105 V

8️ Testing Kontrol RUN / STOP

🔹 Control Word (Register 2001)

Nilai Fungsi
0 STOP
1 RUN

🔹 Reference Speed (Register 2003)

  • Nilai 5000 → 50,00%
  • Jika MaxFreq = 50 Hz → output = 25 Hz

🧪 Langkah Uji:

  1. Write 2001 = 1 → VFD RUN
  2. Write 2003 = 5000
  3. Monitor:
    • Status = RUN
    • Frekuensi = 25 Hz
  4. Write 2001 = 0 → STOP

9️ Indikator Berhasil

✅ Tidak ada error timeout
✅ Status berubah RUN / STOP
✅ Frekuensi & speed berubah sesuai setpoint
✅ Data feedback terbaca stabil

🔚 Kesimpulan

Komunikasi Modbus RTU VFD Vacon 10 berhasil jika:

    • Register dapat dibaca
    • Control Word merespon
    • Scaling sesuai spesifikasi

Related Articles

Leave a Reply